Chapter 5 Instruction Specifications

5-127

Item number

FUN instructions-4

Name

I/O Refresh (slot)

Ladder format

Condition code

Processing time (

µs)

Remark

R7F4

R7F3

R7F2

R7F1

R7F0

Average Maximum

FUN 82 (s)

DER

ERR

SD

V

C

* (SLREF (s))

z

z

z

z

Instruction format

Number of steps

311

Condition

Steps

FUN 82 (s)

3

* (SLREF (s))

Bit

Word

Double word

Usable I/O

X

Y

R,

M

TD, SS,

CU, CT

WX WY

WR,

WM TC DX DY

DR,

DM

C

o

nstant

Other

s

Number of points

{

s+1 and

beyond

Slot location number

{

Designate the slot
location.

Function

s

s+1

s+2

:

:

s+n

Number of points to be refreshed

Refresh slot location number

Refresh slot location number

Refresh slot location number

n

≤ 64

Refresh slot location number is
designated by unit and slot number.

:
:

• Performs refresh of the designated module for the number of points specified by s, starting with area s+1.
• Refresh is performed by slot.
• The slot location numbers stored in areas s+1 and subsequent are designated by the unit number and slot number.
• The maximum number of points to be refreshed (n) is 64 points. The points exceeding 64 points are not refreshed.
• If refresh processing is completed normally, DER is set to “0.”
* ( ) indicates the display when the Ladder Editor is used.

Program example

R000

DIF0

WR0000 = H0002

WR0001 = H0000

WR0002 = H0010

FUN 82 (WR0000)

LD

R000

AND

DIF0

[

WR0000 = H0002

WR0001 = H0000

WR0002 = H0010

FUN82 (WR0000)

]

Program description

• Upon leading of R000, the two slots designated after WR0001 (unit 0, slot 0) and (unit 1, slot 0) are refreshed.

F

UN 82 (s

)

Advertising