Chapter 3 Function and Performance Specifications

3-9

(2) DC output: LCDC-Low Current

(All points of EH-D10DT/DTP, Y102-Y105 of EH-D14DT/DTP, Y102-Y109 of EH-D28DT/DTP,
Y*018-Y*021 of EH-D14EDT/D14EDTP)

Item

Specification

Circuit diagram

Output specification

Transistor output

Rated load voltage

24/12 V DC (+10 %, -15 %)

Minimum switching current

1 mA

Leak current

0.1 mA (max)

1 circuit

0.75 A 24 V DC

0.5 A 12 V DC

Maximum
load current

1 common

3 A

OFF

→ ON

0.1 ms (max) 24 V DC 0.2A

Output
response time ON

→ OFF

0.1 ms (max) 24 V DC 0.2A

Number of output points

See Chapter 4.

Number of common

See Chapter 4.

Surge removing circuit

None

Fuse

None

Insulation system

Photocoupler insulation

Output display

LED (green)

External connection

Removable type screw terminal block (M3)

Externally supplied power *1

30 to 12 V DC

Insulation

1500 V or more (external-internal)

500 V or more (external-external)

Output voltage drop

0.3 V DC (max)

*1:

It is necessary to supply 12 to 30 V DC between the V and C terminals externally. See “4.6 Terminal Layout and Wiring.”

(3) DC output: HCDC-High Current

(Y100,Y101 of EH-D14DT/DTP, Y100, Y101, Y110, and Y111 of EH-D28DT/DTP,
Y*016, Y*017 of EH-D14EDT/D14EDTP)

Item

Specification

Circuit diagram

Output specification

Transistor output

Rated load voltage

24/12 V DC (+10 %, -15 %)

Minimum switching current

1 mA

Leak current

0.1 mA (max)

1 circuit

1A 24 V DC

Maximum
load current

1 common

3 A

OFF

→ ON

0.1 ms (max) 24 V DC 0.2A

Output
response time ON

→ OFF

0.1 ms (max) 24 V DC 0.2A

Number of output points

See Chapter 4.

Number of common

See Chapter 4.

Surge removing circuit

None

Fuse

None

Insulation system

Photocoupler insulation

Output display

LED (green)

External connection

Removable type screw terminal block (M3)

Externally supplied power *1

30 to 12 V DC

Insulation

1500 V or more (external-internal)

500 V or more (external-external)

Output voltage drop

0.3 V DC (max)

*1:

It is necessary to supply 12 to 30 V DC between the V and C terminals externally. See “4.6 Terminal Layout and Wiring.”

In

tern
al circu

it

V0

0

C0

Source type (EH-D**DTP)

Sink type (EH-D**DT)

V0

0

C0

In

tern
al circu

it

In

tern
al circu

it

V0

0

C0

Source type (EH-D**DTP)

Sink type (EH-D**DT)

V0

0

C0

In

tern
al circu

it