Chapter 3 function and performance specifications, 1 general specifications – Hitachi NJI-350B User Manual

Page 17

Advertising
background image

Chapter 3 Function and Performance Specifications

3-1

Chapter 3

Function and Performance
Specifications

3.1

General Specifications

Item

Specification

Power supply type

AC

DC

Power voltage

100/110/120 V AC (50/60 Hz),

200/220/240 V AC (50/60 Hz)

24 V DC

Power voltage fluctuation
range

85 to 264 V AC wide range

19.2 to 30 V DC

Current consumption

Please refer to 4.7, “Weights and Power Consumption.”

Allowable momentary power
failure

85 to 100 V AC:

For a momentary power
failure of less than 10 ms,
operation continues

100 to 264 V AC: For a momentary power

failure of less than 20 ms,
operation continues

19.2 to 30 V DC: For a momentary power

failure of less than 10 ms,
operation continues

Operating ambient temp.

0 to 55

°C

Storage ambient temp.

-10 to 75

°C

Operating ambient humidity

5 to 95 % RH (no condensation)

Storage ambient humidity

5 to 95 % RH (no condensation)

Vibration proof

Conforms to JIS C 0911

Noise resistance

{ Noise voltage 1,500 Vpp Noise pulse width 100 ns, 1

µs

(Noise created by the noise simulator is applied across the power supply module's input

terminals. This is determined by our measuring method.)

{ Based on NEMA ICS 3-304
{ Static noise: 3,000 V at metal exposed area
{ Conforms with EN50081-2 and EN50082-2

Supported standards

Conforms with UL, CE markings and C-TICK

Insulation resistance

20 M

Ω or more between the AC external terminal and the protection earth (PE) terminal (based

on 500 V DC mega)

Dielectric withstand voltage

1,500 V AC for one minute between the AC external terminal and the protection earth (PE)

terminal

Grounding

Class D dedicated grounding (grounded by a power supply module)

Environment used

No corrosive gases and no excessive dirt

Structure

Attached on an open wall

Cooling

Natural air cooling

Advertising