Chapter 12 Error Code List and Special Internal Outputs

12-12

No.

Name

Stored data

Description

Setting

condition

Resetting

condition

WRF06B

Pulse and PWM
output auto
correction setting

01: For EH-***DTP
02: For EH-***DT
03: For EH-***DRP
04: For

EH-***DRT

The output waveforms of the pulses and
PWM are automatically corrected by
setting the value corresponding to the
CPU model.

WRF06C

Potentiometer CH1

WRF06D

Potentiometer CH2

Sampling number: 0 to 40.

WRF06E

Analog input type
selection

Selects whether the analog input is voltage or current.
a: Analog 1 selection

0=Voltage

1=Current

b: Analog 2 selection

0=Voltage

1=Current

WRF06F

Counting mode of
2-phase counter

00: Mode 0 01: Mode 1
02: Mode 2 03: Mode 3

WRF070

I/O operation mode

H00: Mode 0
H01: Mode 1
H02: Mode 2
H03: Mode 3
H10: Mode 10

WRF071

I/O detailed function
settings

I/O assignment for counter, PWM and pulse train output

WRF072

to F075

Output frequency,
On-preset value

Frequency setting value, on-preset setting value

WRF076

to F079

On-duty value,
Off-preset value

On-duty setting value, off-preset setting value

WRF07A

to F07D

Pre-load value,
Pulse output value

Counter pre-load value or pulse output value

WRF07E

Input edge

Counter input edge setting value

WRF07F

Input filtering time

Filter time

×0.5 ms, up to 40 (=20ms)

Set by user

Cleared by
user

WRF080

to F19F

Undefined

Do not use.

*:

See Chapter 8 for more details.

15 14 13

0

a

b

Not used