Chapter 8 High-speed counter, PWM / Pulse train output and Analogue I/O

8-2

8.1.2

Operation Mode

Select one mode from the 5 modes shown in Table 8.1 (mode 10 described in following pages.) and set the mode number
in the special internal output WRF070 when the CPU is in STOP status.

*1: If parameter in WRF070 is not saved by R7F6, the value will be 0 at the next power on.
*2: The operation mode setting can be changed only when CPU is in STOP status.

Each input and output terminal setting is configured in WRF071.

Table 8.1 Operation mode list

Mode 0

Mode 1

Mode 2

Mode 3

Standard

Single-phase counter

×2

Single-phase counter

×4

2-phase counter

×1,

Single-phase counter

×1

X0

Standard input

Counter input 1

Counter input 1

Counter input 1A

Standard input

Counter preload 1

Counter preload 1

Counter preload 1

Interrupt input 1

Counter strobe 1

Counter strobe 1

Counter strobe 1

X1

Standard input

*6

Standard input

*6

Standard input

*6

X2

Standard input

Counter input 2

Counter input 2

Counter input 1B

Standard input

Counter preload 2

Counter preload 2

Counter input (marker) 1Z

Interrupt input 2

Counter strobe 2

Counter strobe 2

X3

Standard input

*6

Standard input

*6

X4

Standard input

Standard input

Counter input 3

Standard input

Standard input

Standard input

Counter preload 3

Standard input

Interrupt input 3

Interrupt input 3

Counter strobe 3

Interrupt input 3

X5

Standard input

*6

Standard input

*6

X6

Standard input

*3

Standard input

*3

Counter input 4

*3

Counter input 4

*3

Standard input

*3

Standard input

*3

Counter preload 4

*3

Counter preload 4

*3

Interrupt input 4

*3

Interrupt input 4

*3

Counter strobe 4

*3

Counter strobe 4

*3

X7

Standard input

*6

Standard input

*6

Standard input

*6

Standard output

Counter output 1

Counter output 1

Counter output 1

PWM output 1

Standard output

*6

Standard output

*6

Standard output

*6

Y100

Pulse output 1
Standard output

Counter output 2

Counter output 2

Standard output

PWM output 2

*5

Standard output

*6

Standard output

*6

PWM output 2

*5

Y101

Pulse output 2

*5

Pulse output 2

*5

Standard output

Standard output

Counter output 3

Standard output

PWM output 3

*5

PWM output 3

*5

Standard output

*6

PWM output 3

*5

Y102

Pulse output 3

*5

Pulse output 3

*5

Pulse output 3

*5

Standard output

Standard output

Counter
output 4

*4

Standard
output

Counter
output 4

*4

Standard
output

PWM output 4

*5

PWM output 4

*5

Std. output

*6

PWM out 4

*5

Std. output

*6

PWM out 4

*5

Y103

Pulse output 4

*5

Pulse output 4

*5

Pulse out 4

*5

Pulse out 4

*5

*3: Modes 0 to 3 can be set regardless of the type of CPU however, note that the 10-point type does not have X6

and X7.

*4: It is only possible to select either Standard output, PWM output, or pulse output for the 10- point type CPU. (A

counter corresponding output cannot be set because there is no counter input that can correspond to it.)

*5: It is possible to set for the relay output type, but the expected output waveform cannot be obtained. Moreover,

care must be taken because it may cause an relay error.

*6: This assignment is supported by Ver.1.11 (WRF051=H0111) or newer.

Advertising