Chapter 5 Instruction Specifications

5-129

Item number

FUN instructions-5

Name

High-speed Counter Operation Control

Ladder format

Condition code

Processing time (

µs)

Remark

R7F4

R7F3

R7F2

R7F1

R7F0

Average Maximum

FUN 140 (s)

DER

ERR

SD

V

C

z

z

z

z

Instruction format

Number of steps

147

Condition

Steps

FUN 140 (s)

3

Bit

Word

Double word

Usable I/O

X

Y

R,

M

TD, SS,

CU, CT

WX WY

WR,

WM TC DX DY

DR,

DM

C

o

nstant

Other

s

Argument (Counter
number, operation
control value)

{

Function

Counter number:

H01 to H04

Operation instruction: H00 – Stop,

H01 – Start

• Performs the starting and stopping of the count operation for the specified counter.

Notes

• If a value other than H01 to H04 is specified for the counter number and the operation instruction is set to a value other than

H00 or H01, DER will be set to “1” and no processing will be performed.

• If the specified counter number is set to a function other than a corresponding external I/O counter (single-phase counter,

two-phase counter), DER will be set to “1” and no processing will be performed.

• Since Counter 4 is invalid when a 10-point CPU is used, if Counter 4 is specified, DER will be set to “1” and no processing

will be performed.

• If the specified counter number is unable to make an output (PI/O function setting result by R7F5), DER will be set to “1”

and no processing will be performed.

• This instruction is only used to start and stop the counter operation. Other counter settings will not be changed.
• The counter operation will start after the power is turned back on even if the power is turned off when the count operation is

stopped by this instruction. The operation of the high-speed counter will be stopped only when this instruction specifies the
stop instruction.

• The counter operation will continue when the CPU operation is stopped.
• When the count operation stops, the progress value update also stops. When starting the count operation, the progress value

is cleared and then the operation starts.

Program example

R0

LD

R0

AND DIF0
[
WR0 = H101
FUN 140 ( WR0 )
]

DIF0

WR0 = H0101
FUN 140 (WR0)

Program description

• Prior to starting a counter operation, various settings required for the counter operation are reflected in the special internal

outputs, and the PI/O function setting flag (R7F5) is turned on while the CPU is being stopped.
For details on the special internal output settings, see Chapter 8.
Starts the counter No. 1 operation.