1 error codes – Hitachi NJI-350B User Manual

Page 264

Advertising
background image

Chapter 12 Error Code List and Special Internal Outputs

12-1

Chapter 12 Error Code List and Special Internal

Outputs

12.1 Error Codes

The table below indicates the self-diagnostic error codes. (See Chapter 13, “Troubleshooting” about corrective actions.)
Error codes are output as hexadecimal values to the special internal output WRF000. (This special internal output is
saved during power failure, and is retained even when the causes of the error are eliminated. Also, when multiple errors
occur, the most fatal error in the error classification is stored.)
Note: LED examples

The occurrence of a flashing pattern other than the following means a micro computer error.

However, an error code is not reflected in the special internal output in this case.

: ON

: OFF

: Flashing (1 s ON, 1 s OFF)

: Flashing (500 ms ON, 500 ms OFF)

: Flashing (250 ms ON, 250 ms OFF)

Related special

internal output

Error
code

Error name

[detection timing]

Classifi

-cation

Description

RUN

LED

OK

LED

Ope-

ration

Bit

Word

11

System ROM error
[at power ON]

Fatal
error

The system ROM has a checksum
error or cannot be read
Error in built-in ROM/FLASH )

Stop

12

System RAM error
[at power ON]

Fatal
error

The system RAM cannot be read
and/or written properly

Stop

13

Micro computer error
[always checking]

Fatal
error

Address error interrupt, undefined
instruction interrupt occurred in the
micro computer

Stop

R7C8

Reset processing in
progress
[at power ON]

CPU is being reset.

Stop

1F

System program error
[always checking]

Fatal
error

System program in FLASH memory
has a checksum error

Stop

23

Undefined instruction
[at starting RUN]

Serious

error

Error is detected when an attempt is
made to execute a user program
instruction that cannot be decoded
(undefined instruction)

Stop

R7C9

27

Data memory error
[at power ON and
initializing CPU]

Serious

error

Data memory cannot be read/written
properly.

Stop

31

User memory error
[at power ON and during
RUN]

Serious

error

A checksum error is detected in user
memory.

Stop

R7CA

33

User memory size error
[at starting RUN]

Serious

error

User program capacity set by the
parameter is other than 280 HEX.

Stop

R7CC

34

Grammar/assemble error
[at starting RUN and
online change in RUN]

Serious

error

There is a grammatical error in user
program.

Stop

R7D4

WRF001

41

I/O configuration error
[always checking]

Minor

error

• I/O assignment information and

actual loading of module do not
match

• Assignment is made for expansion

level 5 or greater.

• There exists assignment of 5 slots or

greater.

*1

Stop

*2

R7CD

WRF002

44

Overload error
(normal scan)
[at END processing]

Minor

error

Execution time for normal scan
exceeded the overload check time set
by the parameter.

*1

Stop

*2

R7D1

45

Overload error
(periodical scan)
[periodical processing]

Minor

error

Execution time for periodical scan
exceeded the execution period.

*1

Stop

*2

R7D2

46

Overload error
(interrupt scan)
[during interrupt
processing]

Minor

error

An interrupt of the same cause
occurred during interrupt scan

*1

Stop

*2

R7D3

Advertising