11 analogue expansion unit – Hitachi NJI-350B User Manual

Page 233

Advertising
background image

Chapter 8 High-speed counter, PWM / Pulse train output and Analogue I/O

8-24

8.11 Analogue Expansion unit

Analogue expansion module has 4 ch. of analog input and 2 ch. of analog output, which is configured by dip switches.

„

Range setting

Analogue input range setting (Common for all input channels.)

Sw1

Sw2

Range

Remarks

off

off

0 - 10V

Default setting

off

ON

0 -

±10V

ON

off

0 - 20mA

ON

ON

4 - 20mA

Analogue output range setting (Common for all output channels.)

Sw3

Sw4

Range

Remarks

off

off

Default setting

off

ON

0 - 10V

ON

off

0 - 20mA

ON

ON

4 - 20mA

Conversino mode

Sw6

Conversion mode

Remarks

off

4,096 (H0FFF)

ON

4,000 (H0FA0)

Default setting

Sw5,7,8 : Set off always.

„

I/O assignment, data table

I/O assignment = "FUN 0"

WX u00

System area

Do not use this area.

WX u01

Ch.1 Input data

WX u02

Ch.2 Input data

WX u03

Ch.3 Input data

WX u04

Ch.4 Input data

Data in lower 12 bits.
Always 0 in higher 4 bits.
0000H - 0FFFH

WY u05

System area

Do not use this area.

WY u06

Ch.6 Output data

WY u07

Ch.7 Output data

Data to be written in lower 12 bits.
0000H -0FFFH

u : Unit number (1 - 4)

Example : Unit 1, Input ch.2

→ WX102 Unit 4, Output ch.7 → WY407

„

In/output data table

0 - 10V / 0 - 20mA / 4 - 20mA

Mode 4000

Mode 4096

0V / 0mA / 4mA

0

0

5V / 10mA / 12mA

H07D0 (2000)

H07FF (2047)

10V / 20mA / 20mA

H0FA0 (4000)

H0FFF (4095)

-10 - +10V (only for analog input)

Mode 4000

Mode 4096

-10V

H0830 (-2000) *

H0800 (-2048) *

0V

0

0

+10V

H07D0 (2000)

H07FF (2047)

* 2's complement

SW1

→ 1

O

N

OFF

ON

Dip switch

(Default setting)

Caution : Set dip switch while power off.

SW2

→ 2

SW3

→ 3

SW4

→ 4

SW5

→ 5

SW6

→ 6

SW7

→ 7

SW8

→ 8

Advertising