Chapter 6 I/O Specifications

6-1

Chapter 6

I/O Specifications

Table 6.1 lists the input/output classifications and input/output point types that can be used with the MICRO-EH

Table 6.1 Usable I/O classifications and point types

10-point

type

14-point

type

23-point

type

28-point

type

Ite

m

Function

S

ym

bol

Siz

e

10/

16

Name

Number of

points

Number of

points

Number of

points

Number of

points

1

External I/O

X

B

10 Bit external input

6 points

8 points

13 points

16 points

WX

W

16 Word external input

1 word

1 word

1 word

2 words

DX

D

16 Double-word external input

Y

B

10 Bit external output

4 points

6 points

10 points

12 points

WY

W

16 Word external output

1 word

1 word

1 word

1 word

DY

D

16 Double-word external output

Analog input

WX

W

16 Analog input

-

-

2 words

-

Analog output

WY

W

16 Analog output

-

-

1 word

-

Counter input

X

B

10 High-speed counter input

3 points

4 points

4 points

4 points

Interrupt input

X

B

10 Interrupt input

total

total

total

total

Counter
output

Y

B

10 High-speed counter synchronized

output

3 points

4 points

4 points

4 points

Ex

tern

al I/O

*

Pulse/PWM
output

Y

B

10 Pulse output

PWM output

3 point

4 points

4 point

4 points

2

Bit

R

B

16 Bit internal output

1984 points

R

B

16 Bit special internal output

64 points

Word

WR

W

16 Word internal output

4096 words

DR

D

16 Double-word internal output

WR

W

16 Word special internal output

512 words

DR

D

16 D.-word special internal output

Sharing of

M

B

16 Bit internal output

16384 points

bit / word

WM

W

16 Word internal output

1024 words

In

tern

al I/O

DM

D

16 Double-word internal output

3

Edge detection DIF

B

10 Rising edge

512 points

DFN

B

10 Falling edge

512 points

Master control MCS

B

10 Master control set

50 points

MCR

B

10 Master control reset

Timer counter

TD

B

10 On delay timer

SS

B

10 Single-shot timer

CU

B

10 Up counter

CTU

B

10 Up-down counter up input

CTD

B

10 Up-down counter down input

Oth

ers

CL

B

10 Clear progress value

Timer 256 points (0.01 s timer has only 0 to 63)
Counter 256 points (The same area as the timer is used.)
(The same timer counter number cannot be used more
than once.)

*: The external I/O, counter I/O, interrupt input, pulse/PWM outputs use the same area by specifying the operation I/O

operation mode (WRF070). See Chapter 8 for further information.

Note: The MICRO-EH does not support CPU link area (L/WL).

Note: B and W in the Size column represent bit and word (16 bits), respectively.