Hitachi NJI-350B User Manual

Page 250

Advertising
background image

Chapter 10 PLC Installation, Mounting, Wiring

10-5

(5)

Wiring to the input terminals

DC input

AC input

3]

4]

6]

C1

0 V

C0

5]

7]

24 V DC

0]

24+

2]

1]

Current output type

Proximity switch

Example of 14-point type

C1

C0

0

Example of 14-point type

Figure 10.5 Input wiring

(a)

DC input
1] When all input terminals (X0, X1, ...) and the common terminal (C) are loaded with 24 VDC, the input

becomes ON status, and approximately 7.5 mA of current flows to the external input contacts.

2] For sensors such as a proximity switch or photoelectric switch, current output type (transistor open

collector) can be connected directly. For voltage-output-type sensors, connect them to the input terminal
after first going through the transistor.

3] Take measures to prevent faulty contact in a strong electric contact.

C

3 W

560

24 V DC

1]

Strong electric
contact

Approx. 50 mA

DC input module

The current that flows to a contact when external contacts
are closed is approximately 7.5 mA. If a strong electric
contact must be used, add resistance as shown in the diagram
at left and supply sufficient current to the contact to prevent
a faulty contact.

4] Limit the wiring length within 30 m.
5] Multiple number of common terminals located at each input section are not connected internally. Make

the connections externally as needed.

6] There are no RUN and STOP switches for the 10-point type. Connect with the RUN input terminal

according to the above connection procedure so that RUN and STOP can be performed. Operation cannot
be performed unless this connection is done.

(b) AC input

In case of AC input module, input voltage may exist if input wiring is long although no device drives. This
phenomenon is caused from leakage current due to floating capacitance between lines.

External

device

AC input

module

The countermeasures are [1] or [2] as follows. This voltage due to electrostatic coupling must be half of max.
OFF voltage or less.

[1] To install dummy resistor in parallel so that impedance of input module is lower.

[2] To replace power supply at drive (external device) side.

External

device

AC input

module

Dummy resistor

Advertising