Chapter 5 Instruction Specifications

5-128

Notes

• Set the unit number (0 to 3) and slot number (0 to 1) after s+1. For other set values, DER is set to “1” and that slot will not

be processed.

• If there is no I/O assignment to the designated slot, DER is set to “1” and that slot will not be processed.
• If the number of s+n points exceeds the maximum I/O number, DER is set to “1” and no processing will be performed.
• If the number of points exceeds 64, DER is set to “1” and the points exceeding 64 will not be processed (refresh will be

performed for up to 64 points).

Slot location number

The slot locations are designated using the unit number and slot number.
The unit number and slot number are set as follows in one word units:

0 to 0

b12

b15

b7

b3

b0

0 to 0

Unit number

Slot number

FUN 82 (s

)