Chapter 5 Instruction specifications

5-122

[3] Address of sending area :

Address number and address type are configured in 2 words as below.

s+4

s+5

Type : WR

→ H000A

I/O No.: H0000 -

WM

→ H000C

[4] Reserved data size for data sending. : This is not actual data size but reserved size. Set it by "Word".

[5] Address of receiving area :

Address number and address type are configured in 2 words as below.
(Data format is as same as sending area.)

[6] Reserved data size for data receiving. : This is not actual data size but reserved size. Set it by "Word".

[7]

*1

Receiving data length :

If receiving data is found by data length, set this parameter by "Byte". The maximum size is 1,024 byte. If data is
more than 1,024 bytes or reserved area, RECV command fails with DER="1".

[8]

*1

Start code :

If receiving data is found by start code, set this parameter. (See TRNS command)

[9]

*1

End code :

If receiving data is found by end code, set this parameter. (See TRNS command)

[10] Communication speed (See TRNS command)

[11] Communication format (See TRNS command)

*1

Received data is defined by either of following 4 ways depending on setting in [7] s+A to [9] s+C.

*2

In case of start code used, CPU can fail to receive due to buffer size full if data with wrong start code is sent.

R

E

C

V

0

(

d, s, t)