Hitachi NJI-350B User Manual

Page 163

Advertising
background image

Chapter 5 Instruction Specifications

5-113

Item number

Control instructions-12

Name

End interrupt scan program (RETURN INTERRUPT)

Ladder format

Condition code

Processing time (

µs)

Remark

R7F4

R7F3

R7F2

R7F1

R7F0

Average Maximum

RTI

DER

ERR

SD

V

C

z

z

z

z

z

Instruction format

Number of steps

0.5

Condition

Steps

RTI

1

Bit

Word

Double word

Usable I/O

X

Y

R,

M

TD, SS,

CU, CT

WX WY

WR,

WM TC DX DY

DR,

DM

C

o

nstant

Other

Function

• This instruction declares the end of an interrupt scan program.
• When this program is executed, the processing is returned to the program that was executing before the interrupt scan was

performed.

• Do not set a startup condition with this instruction.

Notes

• This instruction is checked prior to execution, and when there is an error, the following error code is set in the special

internal output WRF001. Also, the CPU error code '34' is set to special internal output WRF000.

CPU error code

Special internal output

Error code

Error description

H0012

RTI undefined

34

WRF001

H0021

RTI area error

H0031

RTI startup condition error

Instruction for use

INT 0

WR0000=WR0000+1

WR0000=0

R000=0

RTI

X00000

X00000

WM000

< =

WR0000

SET

R000

• A 0.01s timer is created using 10 ms interval interrupt.
• WM000, WR0000 and R000 are used for the set value, progress value

and timer coil, respectively.

• When X00000 is off, the progress value and timer coil are cleared.
• When X00000 is on, the progress value increments by 1 every 10 ms.
• The timer coil is turned on upon WM000 is less than or equal to

WR0000.

RT

I

Advertising