Chapter 5 Instruction Specifications

5-124

Item number

FUN instructions-1

Name

General purpose port switching

Ladder format

Condition code

Processing time (

µs)

Remark

R7F4

R7F3

R7F2

R7F1

R7F0

Average Maximum

FUN 5 (s)

DER

ERR

SD

V

C

z

z

z

z

Instruction format

Number of steps

114

-

Condition

Steps

FUN 5 (s)

3

Bit

Word

Double word

Usable I/O

X

Y

R,

M

TD, SS,

CU, CT

WX WY

WR,

WM TC DX DY

DR,

DM

C

o

nstant

Other

s

Argument

{

s+1

(system area)

{

s+2

(system area)

{

Function

This command is to switch dedicated port (programming port) to general purpose port.

S

Port number

Current setting

System area

System area

S+1

S+2

Port number
H01 : Port 1
H02 : Port 2
* Error with the other values

Current setting
H00 : Dedicated port (Programming port)
H01 : Port 1 is general purpose port
H02 : Port 2 is general purpose port

Notes

• General purpose port can be configured only one port. If either port is configured general purpose port, FUN 5 command for

the other port is ignored with DER=1.

• General purpose works only when CPU is in RUN mode. When CPU status is in STOP, the port is automatically switched

back to dedicated port (programming port).

• It is impossible to switch from general purpose to dedicated port while CPU is in RUN status.
• FUN 5 does not work if port 1 is configured as modem mode.

Program example

X00000

DIF0

LD X00000

AND DIF0
[
WR0100 = H0200

]

WR0100 = H0200
FUN 5 (WR0100)

FUN 5 (WR0100)

Program description

Port 2 is switched to general purpose port at rising edge of X0000 input.