3 port 2 – Hitachi NJI-350B User Manual

Page 256

Advertising
background image

Chapter 11 Communication Specifications

11-3

11.3 Port 2

The specifications of port 2 are listed in Table 11.4. 1:n station communication by the high protocol is possible with port 2.
By creating and including a control procedure based on the high protocol on the personal computer which will become the
host, it becomes possible to control a maximum of 32 stations from one host. The systems can thus be configured in several
ways.

Table 11.4 Port 2 specifications

Item

Specification

Dedicated (programming) port

General purpose port

Communication speed

4800, 9600, 19.2 k, 38.4 k bps

300, 600, 1200, 2400, 4800, 9600, 19.2 k,
38.4 k, 57.6 k bps

Communication system

Half duplex

Synchronization

Asynchronous

Startup system

One-sided startup using the host side command

Transmission system

Serial transmission (bit serial transmission)

Transmission code,
configuration

ASCII: 7-bit data, 1 start, 1 stop, even parity

Configured by user

Transmission code outgoing
sequence

Sent out from the lowest bit in character units

Error control

Vertical parity check, checksum, overrun check, framing check

Transmission unit

Message unit (variable length)

Maximum message length

503 bytes (including control characters)
Note: 505 bytes when the station number is used.

1,024 bytes

Control procedure

H-series dedicated procedure (h-protocol)
Standard protocol (transmission control procedure 1),
Simplified protocol (transmission control procedure 2)

Configured by user

Interface

RS-422/485 (maximum cable length: 250 m)

Connector

CPU side: 15-pin D-sub
Cable side: a cable equivalent to 17JE-23150-02(D8B) (DDK Co., Ltd.) is recommended (D-SUB
fitting screw M3

× 0.5)

(1)

Setting port 2

Port 2 is configured by special register WRF03D. The settings can be changed even when port 2 is communicating. The
highest bit (b15) of WRF03D is setting bit.

If station number mode is used, make sure to set the station number from 0 to 31 in BCD code.
Value in WRF03D is saved in FLASH memory when writing flag (R7F6) is turned on. If saved in FLASH memory, it is
not necessary to set again at the next power up.

(Example) Transmission control procedure 2, communication speed 19.2 kbps, and station number 28.
Î WRF03D = HE228 After the setting is completed, WRF03D is changed to H6228. (b15 cleared)

Bit:

15

14

13

12

11

10

9

8

7

6

5

4

3

2

1

0

WRF03D:

a

b

c

0

d

e

Initial value:

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

0

Figure 11.3 Special internal output for setting port 2

Field

Setting value

Content

Note

a

0

Setting completed

After the setting is completed, the
system changes this bit to 0.

1

Setting change request

Set this bit to 1 when changing the
setting.

b

0

Transmission control procedure 1

1

Transmission control procedure 2

c

0

Without station number

1

With station number

d

0

Transmission speed

4800 bps

Setting of bits 8 to 12

H0000

1

9600 bps

H0001

2

19.2 kbps

H0010

3

38.4 kbps

H0011

Other than above

4800 bps

e

0 ~ 31

Station number *

Set by BCD.

* Communication speed of general purpose port is configured in TRNS/RECV command. Value in WRF03D
is ignored.

Advertising