3 performance specifications, 1 calculation specifications – Hitachi NJI-350B User Manual

Page 22

Advertising
background image

Chapter 3 Function and Performance Specifications

3-6

3.3

Performance Specifications

3.3.1

Calculation Specifications

The calculation specifications of the PLC are described below.

Model

Name

10-point type

14-point type

23/28-point type

Type

EH-D10DT
EH-D10DTP
EH-D10DR

EH-D14DT
EH-D14DTP
EH-A14DR
EH-D14DR
EH-A14AS

EH-A23DRP
EH-A23DRT
EH-D23DRP

EH-D28DT
EH-D28DTP
EH-A28DRP
EH-A28DRT
EH-A28DR
EH-D28DRP
EH-D28DRT
EH-D28DR
EH-A28AS

CPU

32-bit RISC processor

Processing system

Stored program cyclic system

Basic instructions

0.9

µs / instruction

Control
specifications

Processing
speed

Application instructions

Several 10

µs / instruction

User program memory

3 k steps max. (FLASH memory)

Instruction
language

Basic instructions

39 types such as LD, LDI, AND, ANI, OR, ORI, ANB, ORB, OUT, MPS,

MRD, MPP, etc.

Operation
processing
specifications

Arithmetic instructions
Application instructions

62 types (arithmetic, application, control, FUN command etc.)

Ladder

Basic instructions

39 types, such as

Arithmetic instructions
Application instructions

62 types (arithmetic, application, control, FUN command etc.)

I/O processing system

Refresh processing

I/O
processing
specifications

External
I/O

Maximum number of
points

10 points

126 points

135 points

140 points

Bit

1,984 points (R0 to R7BF)

Internal
output

Word

4,096 words (WR0 to WRFFF)

Bit

64 points (R7C0 to R7FF)

Special

Word

512 words (WRF000 to WRF1FF)

Bit/word shared

16,384 points, 1,024 words (M0 to M3FFF, WM0 to WM3FF)

Number of points

256 points (TD + CU) *1

Timer
counter

Timer set value

0 to 65,535, timer base 0.01 s, 0.1 s, 1 s (0.01s has maximum 64 points *2)

Counter set value

1 to 65,535 times

Edge detection

512 points (DIF0 to DIF511: Decimal)

+ 512 points (DFN0 to DFN511: Decimal)

Program system

Instruction language, ladder diagram

Peripheral
equipment

Peripheral unit

Programming software

(LADDER EDITOR DOS version/Windows® version, Pro-H)

Instruction language programmer and form graphic display programmer cannot

be used.

Maintenance
functions

Self-diagnosis

PLC error (LED display): Microcomputer error, watchdog timer error, memory
error, program error, system ROM/RAM error, scan time monitoring, battery
voltage low detection, etc.

*1:

The same numbers cannot be used with the timer counter.

*2:

Only timers numbered 0 to 63 can use 0.01 s for their timer base.

Advertising