Hitachi NJI-350B User Manual

Page 277

Advertising
background image

Chapter 13 Troubleshooting

13-2

The following shows the range of the special internal output that is cleared when R7EC is set to “1.”

No.

Bit special internal output

No.

Word special internal output

R7C8

Fatal error flag

WRF000

Self-diagnostic error code

9

Microcomputer error

1

Syntax/assembler error details

A

User memory error

2

I/O verify mismatch details

B

(Undefined)

C

Memory size over

D

I/O verify mismatch

E

(Undefined)

R7CF

(Undefined)

R7D0

(Undefined)

1

Congestion error (normal scan)

2

Congestion error (periodical scan)

3

Congestion error (interrupt scan)

4

Syntax/assembler error

5

(Undefined)

6

(Undefined)

7

(Undefined)

8

(Undefined)

9

Battery error

A

(Undefined)

R7DB

Self-diagnostic error

When all of the special internal output data cannot be cleared during program execution, refer to the self-
diagnostic error code list and clear only the corresponding error flags by using forced set of the programmer
or peripheral unit.

Caution

If the internal output for a self-diagnostic error R7DB (WRF000) is used as a system error for the stop condition of CPU
RUN, the R7DB may be turned on even with an error of the warning level (battery error, etc.), causing the CPU to stop.
Therefore, do not use the internal output of the self-diagnostic error as a condition for stopping the CPU.