Chapter 4 Product lineup and wiring

4-3

4.2

10-Point Basic Unit

Name and function of each part

Type

EH-D10DT, EH-D10DTP, EH-
D10DR

1] POW LED
2] OK LED
3] RUN LED

4] Serial port

5] RUN input

9] Mounting hole

8] Power terminal

7] Output terminals

10] DIN rail installation clip

6] Input terminals

No.

Item

Detailed explanation

Remarks

Explanation of operation

Operations are performed according to the contents of the program created
by the user.
The programming unit connected to the CPU module communication port
writes and reads the user programs.
Memory is installed inside the CPU module in which the user programs and
internal output information are stored.

1]

POW LED

Lighting when the power is supplied.

2]

OK LED

Lighting at normal operation.

See Chapter 12.

3]

RUN LED

Lighting at RUN status.

4]

Serial port 1

Serial port for connecting the peripheral units. Communication speed is
fixed as 4800 bps.
The communication specification is set to port 1.

See Chapter 11.

5]

RUN input

External input to control the PLC’s RUN/STOP.
When 24 V DC is loaded to the RUN terminal and common terminal (C),
the PLC is set to the RUN state.

See Chapter 10.

6]

Input terminals

Terminals for wiring the external input units.
One piece of AWG14 to AWG22 (2.1 to 0.36 mm

2

) or two pieces of

AWG16 to AWG22 (1.3 to 0.36 mm

2

) per terminal may be wired.

See Chapter 10.

7]

Output terminals

Terminals for connecting the external load. The wiring specification is the
same as for the input terminals.

See Chapter 10.

8]

Power terminal

Terminal for connecting the power supply. The wiring specification is the
same as for the input terminals.

See Chapter 10.

9]

Mounting hole

Used when installing the PLC directly on a board with screws

See Chapter 10.

10]

DIN rail
installation clip

Used when installing the PLC on a DIN rail

See Chapter 10.