Chapter 10 PLC Installation, Mounting, Wiring

10-4

(3)

Wiring to the power module

100 V AC to
240 V AC

Power supply
for the sensor

Power leakage
breaker

Shielded
insulated
transformer

Noise

filter

Figure 10.4 Power supply wiring diagram

(a) For power supply wiring, use a cable of 2

mm

2

or more to prevent a voltage drop from

occurring.

(b) For the function ground terminal (PE

terminal), use a cable of 2 mm

2

or more and

provide Class D grounding (100

Ω or less).

The appropriate length for the ground cable
is within 20 m.
1] Instrumentation panel and relay panel

grounding may be shared.

2] Avoid grounding shared with equipment

that may generate noise such as high-
frequency heating furnace, large-scaled
power panel (several kW or more),
thyristor exchanger, electric welders, etc.

3] Connect a noise filter (NF) to the power

cable.

(c) Tighten the terminal screws within the torque

range as shown below.

Unit

Screw

Clamping

torque

10-point

M2.5

0.3 to 0.4 Nxm

14, 23, 28-point,

expansion

M3.0

0.5 to 0.6 Nxm

(d) Use the same power supply system for the

basic and expansion units.

(4)

Wiring cable for I/O signals

6

6

Tighten each terminal screw using a torque of the
specified torque range.
When using a crimp terminal, use one with an
outer diameter of 6 mm or less.
Use only up to two crimp terminals in the same
terminal. Avoid clamping down more than three
at the same time.
Only one piece of cable can be wired per
terminal if the cable type is between AWG14 and
AWG22 (cable thickness ranging between 2.1
mm

2

and 0.36 mm

2

), but two pieces can be wired

if the cable type is between AWG16 and AWG22
(between 1.3 mm

2

and 0.36 mm

2

).