Chapter 10 PLC Installation, Mounting, Wiring

10-7

(a)

Wiring to the relay output terminals
1] Life of relay contacts

Life curve of relay contacts

500

100

10

1

0

1

4

5

50

20

6

3

2

1000

AC 125 V cos

φ =1

AC 125 V cos

φ =0.7

AC 125 V cos

φ =0.4

Sw

itc

hing

lif

e (

10,

000 t

im

es

)

Contact switching current (A)

Figure 1 Life characteristics (125 V AC)

Life of the contact is almost in squared
reverse proportion to the current, so be aware
that interrupting rush current or directly
driving the condenser load will drastically
reduce the life of the relay.
When switching is made with high
frequency, use a transistor output module.

500

100

10

1

0

1

4

5

50

20

6

3

2

1000

AC 250 V cos

φ =1

AC 250 V cos

φ =0.7

AC 250 V cos

φ =0.4

Contact switching current (A)

Figure 2 Life characteristics (250 V AC)

Sw

itc

hing

lif

e (

10,

000 t

im

es

)

500

100

10

1

0

1

4

5

50

20

6

3

2

1000

DC 30 V L/R=1 ms

DV 30 V L/R=7 ms

DC 30 V L/R=15 ms

Figure 3 Life characteristics

Sw

itc

hing

lif

e (

10,

000 t

im

es

)

Contact switching current (A)

2] Surge killer

For inductive load, connect a surge killer (condenser 0.1

µF, + resistance of approx. 100 Ω) in parallel to

the load. Also, for DC load, connect a flywheel diode.

3] Fuse

A built-in fuse is not used in this module. Install a 6 A fuse in the common to prevent the external wiring
from burning out.
For the independent contact output section, install a 2A fuse per circuit.

(b)

Wiring to the transistor output terminals
4] Flywheel diode

For inductive load, connect a flywheel diode in parallel.

5] V and C terminals

Always connect a V terminal and C (common) terminal. If the module is used without connecting these
terminals, the internal flywheel diode may not function and the module may malfunction or break down.

6] Fuse

There is no built-in fuse to prevent external wiring burning. Therefore, it is recommended that a fuse be
installed externally to prevent the external wiring from burning out. (This does not protect the internal
transistor elements.) If the external load is short-circuited, please contact us for repair.