Chapter 5 Instruction Specifications

5-33

Program description

[Time chart]

X00005

CL15

CU15

1

2

3

4

5

65 535

3

Progress
value of
CU15 (TC15)

1]

2]

4]

Set value 4

5]

3]

Ignored

Ignored

1] The progress value (count) is cleared to 0 by the counter

clear (CL15). While the counter clear is on, the progress
value will not be updated.

2] The progress value is updated at the leading edge of

X00005.

3] Counter coil (CU15) is turned on since the progress value

set value.

4] The count value will not exceed 65535 (decimal).
5] The progress value and counter coil are cleared by counter

clear (CL15).

• The clear is performed under the conditions set immediately

prior to the execution of the counter coil instruction.

• Example using word I/O as the set value

When RUN is commenced, the set value is set to the word I/O.
Or, the word I/O for the set value is designated to store in the power failure memory.

O

U

T

CU

n

s

Advertising