Chapter 6 I/O Specifications

6-5

6.3

Internal Output Numbers

Memory is available as an internal output area in the CPU module. There are three areas: bit dedicated area (R), word
dedicated area (WR), and bit/word shared area (M/WM).

Table 6.8 List of I/O number conventions for external I/O

Data type

Numbering convention

Example

Bit-dedicated
type

R

Normal area H000 to H7BF
Special area H7C0 to H7FF
Both are expressed as hexadecimals.

R0
R105
R23C
R7E7

Word dedicated
type

<Word>

WR

Normal area H0000 to
Special area HF000 to
Both are expressed as hexadecimals.

WR0
WR11
WR123
WRF004

<Double word>

DR

Normal area H0000 to
Special area HF000 to
Both are expressed as hexadecimals.
Expresses WR for 2 words in continuation.

DR0
DR11
DR123
DRF004

Bit/word shared
type

<Bit>

M

H0000~

M0
M11
M123

<Word>

WM

H000~

M120F

...........

M1200

WM120

WM0
WM11
WM123

<Double word>

DM

H0000 to
Expresses as hexadecimals.
Expresses DM for 2 words in continuation.

DM0
DM11
DM234

• Internal outputs R, WR and DR are completely separate areas. Bit-based operations cannot be performed in the WR.

(Example) Relationships among R100, WR10, and DR10

DR11

R100

WR11

WR10

DR10

WR/DR area

Another area

R area

• Because internal outputs M, WM and DM share the same area, bit-based operations are allowed.

(Example) Relationships among M100, WM10, and DM10

DM10

M11F

.......

M10F

M110

DM11

M109

M10A

M100

.......

WM11

WM10