Chapter 13 Troubleshooting

13-4

Error code

Error name

Corrective action

61

Port 1 transmission
error (parity)

62

Port 1 transmission
error
(framing/overrun)

Check the connection of the connector cable.
Check the settings such as the transmission speed.
Check to see if there are any sources of noise near the cable.

63

Port 1 transmission
error (timeout)

64

Port 1 transmission
error (protocol error)

65

Port 1 transmission
error (BCC error)

Check the connection of the connector cable.
Check to see if there are any sources of noise near the cable.
Verify the protocol specification, examine the host computer processing and correct any
errors.

67

Port 2 transmission
error (parity)

68

Port 2 transmission
error
(framing/overrun)

Check the connection of the connector cable.
Check the settings such as the transmission speed.
Check to see if there are any sources of noise near the cable.

69

Port 2 transmission
error (timeout)

6A

Port 2 transmission
error (protocol error)

6B

Port 2 transmission
error (BCC error)

Check the connection of the connector cable.
Check to see if there are any sources of noise near the cable.
Verify the protocol specification, examine the host computer processing and correct any
errors.

71

Battery error

Replace the battery with a new one.
Verify the connection of the battery connector.

91

Port 1
Modem no response

Verify the connection with battery.
Replace the modem with a new one.

Perform the following procedures to erase the error display.

(a)

When the basic unit is being stopped
Turn the basic unit RUN switch (or RUN terminal) to “STOP,” then to “RUN” again.
If the cause of the error has been corrected, the OK lamp is lit. However, the error information remains in the
error special internal output, which stores the CPU error types and details. (This makes it possible to analyze
the error after recovery.) To reset the error information, perform the procedures shown in (b) or turn ON the
special internal output (R7EB) of the power failure memory clear on the peripheral units.

(b)

When the CPU is still running (RUN)
Set the special internal output R7EC to “1” to clear the OK lamp indicator and the error internal output.