Chapter 5 Instruction Specifications

5-141

Item number

FUN instructions-15

Name

Pulse frequency output setting changes

Ladder format

Condition code

Processing time (

µs)

Remark

R7F4

R7F3

R7F2

R7F1

R7F0

Average Maximum

FUN 150 (s)

DER

ERR

SD

V

C

z

z

z

z

Instruction format

Number of steps

217

Condition

Steps

FUN 150 (s)

3

Bit

Word

Double word

Usable I/O

X

Y

R,

M

TD, SS,

CU, CT

WX WY

WR,

WM TC DX DY

DR,

DM

C

o

nstant

Other

s

Argument (Pulse
number)

{

s+1

Argument (Frequency
value)

{

s+2

Argument (Number of
output pulses)

{

Function

Pulse output number:

H01 to H04

Change specification:

H00: Sets the frequency value and

number of pulse output,

H01: Sets the frequency value

only,

H02: Sets the number of pulse

output

Frequency: 10 to 5000 (Hz)
* The maximum frequency of 5000 Hz represents the total of

all pulse output frequencies.

* If the frequency value is set to less than 10 Hz, it is

internally changed to 10 Hz. The S parameter is also
rewritten.

Number of output pulses: H0000 – HFFFF (0 to 65535)

Auto correction is executed when the value corresponding to
the CPU model is specified in WRF06B.
Caution: There will be a slight error even if correction setting

is performed.

• Pulse output is commenced at the specified frequency. Output is stopped once the number of pulses specified have been

output.

• Sets the frequency value in Hz.

Example: To set a frequency of 3 kHz, set 3000 (HBB8) as internal output.

• Sets the count for the number of output pulses.

Example: To set output of 10,000, set 10,000 (H2710) as internal output.

S

15

0

S + 1

Frequency value

S + 2

Number of pulse output

Pulse output number

Change specification

FUN 150 (s

)