Chapter 12 Error Code List and Special Internal Outputs

12-5

12.4 Bit Special Internal Output Area

The MICRO-EH has a special internal output area for performing status display and various other settings. The special
internal output area is constantly backed up in case of power failure.
The following lists the definitions of the bit special internal output area (R7C0 to R7FF).

No.

Name

Meaning

Description

Setting

condition

Resetting

condition

R7C0 Ignore scan time

error (normal scan)

0: Stop operation
1: Continue operation

Designates continue/stop running when
a normal scan overload error occurs

R7C1 Ignore scan time

error (cyclic scan)

0: Stop operation
1: Continue operation

Designates continue/stop running when
a periodic-scan overload error occurs

Set by user

R7C2 Ignore scan time

error (interrupt scan)

0: Stop operation
1: Continue operation

Designates continue/stop running when
an interrupt-scan overload error occurs

Cleared by
user, Cleared
when
retentive area
is cleared, or
the CPU is
initialized.

R7C3 Undefined

Do not use.

R7C4 Undefined

Do not use.

R7C5 Undefined

Do not use.

R7C6 Undefined

Do not use.

R7C7 On line change in

RUN

0: On line changed not

allowed.

1: On line changed

allowed.

Designates whether online change in
RUN is allowed in user program

Set by user

R7C8 Serious error flag

0: Normal
1: Abnormal

Indicates whether there is an abnormal
in the microcomputer
(Address error, undefined instruction)

R7C9 Microcomputer error 0: Normal

1: Abnormal

Indicates whether there is an abnormal
in the microcomputer
(Computation error)

R7CA User memory error

0: Normal
1: Abnormal

Indicates whether there is an abnormal
in user memory

Set by the
system

Cleared by
user, Cleared
when
retentive area
is cleared, or
the CPU is
initialized.

R7CB Undefined

Do not use.

R7CC Memory size over

0: Normal
1: Abnormal

Indicates whether the capacity set by
the parameter exceeds loaded memory
capacity

R7CD I/O configuration

error

0: Normal
1: Unmatched

Indicates whether I/O assignment and
loading are matched (Mismatched
information output to WRF002)

Set by the
system

Cleared by
user, Cleared
when
retentive area
is cleared, or
the CPU is
initialized.

R7CE Undefined

Do not use.

R7CF

*1

Operation mode for
instantaneous power
failure

0: Hold
1: Reset (same start up operation as normal power on.)

Set by the
system

Cleared by
user, Cleared
when retentive
area is cleared,
or the CPU is
initialized.

R7D0 Undefined

Do not use.

R7D1 Scan time error

(normal scan)

0: Normal
1: Scan time over

Indicates whether the normal scan
execution time has exceeded the
designated time

R7D2 Scan time error

(cyclic scan)

0: Normal
1: Scan time over

Indicates whether the periodic scan was
completed within cycle time

R7D3 Scan time error

(interrupt scan)

0: Normal
1: Scan time over

Indicates whether an interrupt of the
same factor occurred during interrupt
scan execution.

R7D4 Grammar/assemble

error

0: Normal
1: Error

Indicates whether there is a grammar
error in user program (Detailed
information output to WRF001)

Set by the
system

Cleared by
user, Cleared
when
retentive area
is cleared, or
the CPU is
initialized.

R7D5 Blown fuse detection 0: Normal

1: Error

Indicates whether or not a fuse
connected to the second pin (see
Chapter 11) of serial port 1 has blown
out.

Set by the
system

Cleared by
the system

R7D6 Undefined

Do not use.

*1:

Supported by software version 1.11 (WRF051=H0111) or newer.