13

5.1 General technical data

ambient temperature:

0° C ... +40° C, 32º F... +104º F

At higher temperatures reduce the output current as shown below or

upsize to the next largest HYDROVAR.

The enclosure rating of the HYDROVAR is IP55 however, please note

the following:

• Protect the HYDROVAR from direct sunlight!

• Protect the HYDROVAR from direct rainfall

• Outdoor installation without protection from sun will void warranty!

storage temperature:

-25° C ... +55° C, -10º F ... +130º F

Humidity:

RH maximum 50% at 104º F, unlimited

RH maximum 90% at 70º F, maximum 30 days per year

75% average per year (class F)

Condensation is not allowed and will void warranty!

During long periods of inactivity or shutdown, the HYDROVAR should

remain connected to the power supply but turned off to prevent

inadvertant pump run. This will maintain power to the internal heater and

reduce internal condensation.

air pollution:

The air may contain dry dust as found in workshops where there is

excessive dust due to machines. Excessive amounts of dust, acids,

corrosive gases, salts etc. are not permitted

altitude:

Maximum 1000 m, 3280 feet above sea level.

At sites over 1000 m above sea level, the maximum output power should

be de-rated by 1% for every additional 100 m. For installations higher

than 2000 m above sea level, please contact your local distributor.

class of protection:

IP 55, NEMA 4 (Indoor use only)

Certifications:

CE, UL, C-Tick, cUL

0

10

20

30

40

50

60

70

80

90

100

110

0

10

20

30

40

50

60

Maximum Ambient Temperature (ºC)

Maximum Output Curr

ent (%

)

tecHnical data