22 SELECT DEVICE

Select device

* 1 *

Possible settings:

1-8

Check the current status, the motor hours and the most recent failures of any given drive. The drive selec-
tion is determined by the current selected mode [105]. Select desired unit by pressing ▲ or ▼.

cascade serial/sYncHron:
The selection specifies the address of the HYDROVAR units

E.g. Device 1 -> Master Inverter with pre-selected address 1

Device 2 -> Basic Inverter with pre-selected address 2

Device 3 -> Basic Inverter with pre-selected address 3

To set the address on a Basic Inverter, see chapter addressing.
To set the address on a Master Inverter, see parameter [106] or submenu [1200] RS485-Interface.

Mode cascade relaY:
device

enabled By

1

Master Inverter

2

fixed speed pump

Relay 1

X10: 1

3

fixed speed pump

Relay 2

X10: 2

4

fixed speed pump

Relay 3

X10: 3

5

fixed speed pump

Relay 4

X10: 4

6

fixed speed pump

Relay 5

X10: 5

7

not used

8

not used

23

23 STATUS DEVICE

Status of the selected device

Stopped

Possible messages: Running, Stopped, Disabled, OFF, Preparing

(Mode Casc. Serial/Synchr)

relay on, relay off

(Mode: Cascade Relay)

Solorun, Faulted

(all Modes)

Shows the status of the device

Mode cascade relaY:
relay_on

->

Relay contact is closed -> fixed-speed-pump is running

relay_off

->

Relay contact is opened -> fixed-speed-pump is stopped

Mode cascade serial/sYncHron:
running

->

Pump is running

stopped

->

Pump is stopped

disabled

->

Pump is disabled by an external input.

(Stopped with buttons or disabled with parameter ENABLE DEVICE [24]) or by external

on/off contact open

preparing ->

A new unit is connected to the multi-pump system and Data is being transferred

solo run

->

Solorun (Hand Mode) is activated (XSL closed)

faulted

->

A failure has occurred on the current unit

S

G

S