Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 57

Advertising
background image

57

G

G

G

S

S

S

S

S

calculations of the new required value for multi pump applications:
k ... number of active pumps (k >1)
p = p

set

+ (k-1)*[lift value – fall value]

• Lift value = Fall value

pressure constant independent of how many pumps are in operation

• Lift value > Fall value

pressure rises when assist pump switches on

• Lift value < Fall value

pressure falls when assist pump switches on

The following 3 parameters are responsible for starting the assist pumps and to calculate the new required
value.

0505

0505 ACT. VAL. INC.

Lift value

5 PSI

Possible settings:

0.00 – to the pre selected sensor range

0510

0510 ACT. VAL. DEC.

Drop value

2 PSI

Possible settings:

0.00– to the pre selected sensor range

0515

0515 ENABLE FRQ

Enable frequency for the next drive

48.0 Hz

Possible settings:

0.0 – 70.0 Hz

Sets the frequency for the next pump to turn on. If a pump in the system reaches this frequency and the
system pressure drops below the REQUIRED VALUE [02] - ACTUAL VALUE DECREASE [0510], the next
pump is started.

0520

0520 ENABLE DLY

Enable delay time (for cascade relay only!)

5 sec

Possible settings:

0 – 100 sec

Delay, in seconds, after the current pump reaches the enable frequency, before the next pump turns on.

0525

0525 SW DELAY

Switch delay (for cascade relay only!)

5 sec

Possible settings:

0 – 100 sec

Delay time between two switching actions of the fix speed pump. The parameter prevents the system re-
peated switching actions caused by varying demand.