0400 suBMenu

sensor

In this submenu all actual value sensors which are connected to the HYDROVAR can be configured, (up to
two transducers with current output or voltage signal output).

Two different transducer types can not be used because the configuration is the same for all connected
sensors. Transducers must be always the same type.

0405

0405 DIMENS. UNIT

Dimension unit

PSI

Possible settings: bar, psi, m

3

/h, g/min, mH2O, ft, °C, °F, l/sec, l/min, m/sec, …, %

Choose the desired Dimension Unit by pressing ▲ or ▼.
When DIMENSION UNIT, you must also change the SENSOR RANGE [0420] according to the new DIMEN-
SION UNIT!

0410

0410 CONF SENSOR

Selection of the sensor

Sensor 1

Possible settings:

- Sensor 1

- Sensor 2

- Auto

- Switch Dig 1

- Switch Dig 2

- Switch Dig 3

- Switch Dig 4

- Auto Lower

- Auto Higher

- (Sensor 1 – Sensor 2)

This parameter determines how the connected sensors are used and which one is active. It is also possible
to measure the difference of two connected sensors or to configure an automatic switchover in case of a
faulty sensor.

Sensor 1 is constantly active.

Sensor 1

0/4-20mA signal ……. connected to X3/2 and X3/3 (+24V)

0-10V signal ……. connected to X3/6 and X3/3 (+24V)

Sensor 2 is constantly active.

Sensor 2

0/4-20mA signal ……. connected to X3/4 and X3/3 (+24V)

0-10V signal ……. connected to X3/5 and X3/3 (+24V)

Auto

Automatic switch over in case of a faulty transducer.

Switch Dig1

Manual switching by closing digital input 1 (X3/9-10)

Switch Dig2

Manual switching by closing digital input 2 (X3/6-GND)

Switch Dig3

Manual switching by closing digital input 3 (X3/5-GND)

Switch Dig4

Manual switching by closing digital input 4 (X3/15-GND)

Auto Lower

The sensor with the lower actual value (or available sensor in case of a faulty

sensor) is used automatically

Auto Higher

The sensor with the higher actual value (or available sensor in case of a faulty

sensor) is used automatically

Sens.1 – Sens.2

The difference between connected sensors is taken as actual value

proGraMMinG