Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 56

Advertising
background image

56

S

S

S

H

Q

0

0

P

1

P

1 +2

P

1 +2+3

0440

0440 SENS 2 CAL 0

Sensor 2 zero point calibration

0% = actual value

Possible settings:

- 10% up to +10%

Zero point calibration for Sensor 2, for explanation see Parameter 0430.

0445

0445 SENS 2 CAL X

Sensor 2 upper range value calibration

0% = actual value

Possible settings:

- 10% up to +10%

Upper range calibrations for Sensor 2, for explanation see Parameter 0435.

0500

0500 suBMenu

seQuence cntr.

This submenu defines parameters for multi-pump systems.

application example:
1) Lead pump reaches its ENABLE FREQUENCY [0515]
2) Actual value falls and reaches the cut in-value of the 1st assist pump Cut in-value = REQUIRED VALUE

[02] – ACT. VAL. DEC. [0510]

the 1st assist pump is switched on automatically

3) After the start up the new required value is calculated in the following way:

NEW REQUIRED VALUE = REQ. VAL. [02] – ACT. VAL. DEC [0510] + ACT. VAL. INC. [0505].
The new required value is shown in the main menu as parameter EFF. REQ. VAL. [03].