5.2 eMc requirements (electromagnetic compatibility)
The EMC requirements depend on the intended use.

class B environment (en 61800-3: class c2)
Environment that includes domestic premises, it also includes establishments directly connected without in-
termediate transformers to a low-voltage power supply network which supplies buildings used for domestic
purposes. Examples of class B environments include houses, apartments, commercial premises or offices in a
residential building.

caution: The relevant EMC regulations for which the HYDROVAR was tested in class B environments is based
on the restricted use of the product and the following limitations:1) the drive voltage is less than 1000 V; 2) it
is neither a plug in device nor a movable device and, 3) when used in the class B environment, it is intended to
be installed and utilized by technicians with the necessary training and skills required for installing and/or using
power drive systems, including specific training with respect to EMC requirements.

class a environment (en 61800-3: class c3)
Environment that includes all establishments other than those directly connected to a low voltage power supply
network which supplies buildings used for domestic purposes e.g. Industrial areas, technical areas of any build-
ing fed from a dedicated transformer are typical examples of class A environment locations.

the HYdroVar complies with the general eMc regulations and is tested according to the following

standards: en 61800-3/2004
en 55011 (2002)

Disturbance voltages / Disturbance field strength

First environment

second environment

– class B / class C2

– class A / class C3

Disturbance voltages

OK

OK

Disturbance field strength

*

OK

* Warning - In a domestic environment, this product may cause radio interference, in which case supplementary mitigation measures

may be required.

en 61000-4-2 (2001)

Electrostatic discharge

en 61000-4-3 (2002)

Electromagnetic field immunity test

en 61000-4-4 (2001)

Burst immunity test

en 61000-4-5 (2001)

Surge immunity test

en 61000-4-6 (1996)

Immunity of conducted RF-Disturbance