0530

0530 DISABLE FRQ

Disable frequency (for cascade relay only!)

30 Hz

Possible settings:

0.0 – 120.0 Hz

The frequency to switch off the fixed speed pumps in cascade relay-mode.

If the Master Inverter goes below that frequency for longer than the pre-selected DISABLE DLY [0535] and
the system pressure is higher than the EFFECTIVE REQ. VALUE [03] (REQUIRED VALUE [02] + ACTUAL VAL.
INC [0505]), the first assist pump stops.

0535

0535 DISABLE DLY

Disable delay time (for cascade relay only!)

5 sec

Possible settings:

0 – 100 sec

Delay time before switching off the assist pumps in cascade relay mode.

0540

0540 DROP FRQ

Drop frequency (for cascade relay only!)

42 Hz

Possible settings:

0.0 – 70.0 Hz

This parameter is used to prevent the system from pressure hammers. Before a following pump starts up,
the Master Inverter will drop to the selected frequency. If the DROP FREQUENCY is reached, the follow-up-
pump gets released and the Master Inverter will continue with normal operation.

0545

0545 OVERVALUE

Overvalue (for cascade relay only!)

OFF

Possible settings:

OFF – pre selected sensor range

If this selected value is reached, an immediate shut-off of the fixed speed pumps is executed.
E.g.

REQUIRED VALUE [02]: 70 PSI

OVERVALUE [0545]:

100 PSI

If three pumps are running (1 Master Inverter + 2 fixed speed pumps) and a system pressure of 100 PSI is
reached, one after another assist pump is switched off.

This parameter prevents the system against overpressure in case the HYDROVAR has been parameterized
incorrectly.

0550

0550 OVERVAL DLY

Overvalue delay (for cascade relay only!)

0 sec

Possible settings:

0.0 – 10.0 sec

Delay time to switch off an assist pump in case the actual value exceeds the OVERVALUE [0545] limit.