Electrical installation and wiring – Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 27

Advertising
background image

27

terminating control Wires:
- Use recommended cable type (see section 8.2)
- Strip the end of the wire aproximately 1/4"
- Push down the orange wedges using a small screwdriver
- Insert the stripped wire
- Remove the screwdriver to complete the connection
- To remove, push down the orange wedges and pull out the wire!

connection example using one Master and three Basic drives:

8.4.3.2 addressing
When using the cascade serial/synchron mode in a multi-pump-application (where more than drive is used),
each drive must be addressed correctly.
Master drive – The address of the Master drive is set using the Hydrovar software. Dip switches are used to
program the Basic drives to a specific address. On all Master drives the dip switches must be set to address 1
(default setting, see below).
Basic drive – When using a Basic drive in a Multi-pump-system the dip switches must be set to the appropri-
ate address for each drive in the system. The addresses for the Basic drives start after the last address of the
final Master drive in the system. The S1 switchbank is located on the lower board behind the control panel.
(See pictures below for locations.)

Example:

Multi-pump-system with 3 Master and 4 Basic drives

• Set address 1-3 for the Master Inverters via appropriate software parameters (See submenu CONF

INVERTER [0100] or submenu RS485-INTERFACE [1200])

• Address 4-7 for the Basic Inverters via dip-switches

The pre-selected address also defines the initial pump sequence.
HVB 1202 / 1203, HVB 3403 / 3405

HVB 3407 / 3410 / 3415

Basic inverter

Basic inverter

GND

SIO +

SIO -

GND

SIO +

SIO -

GND

SIO +

SIO -

GND

SIO +

SIO -

6

5

4

X4

X2

X2

X2

HYDROVAR Master Inverter
Control Card

HYDROVAR Basic Inverter
Power Unit

HYDROVAR Basic Inverter
Power Unit

HYDROVAR Basic Inverter
Power Unit

electrical installation and WirinG