Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 26

Advertising
background image

26

connection example

external switch to enable the

solo run (Hand Mode)

example:

low water or other

emergency off switch

thermistor

(mounted in the motor terminal box)

recommended connections of external protective devices:

Basic drive

Thermistor

X1/PTC

Emergency switch

X1/PTC

As described above

Low water switch

X1/PTC

Master drive

Thermistor

X1/PTC

As described above

External release

X3/7-8

On the control card

Low water switch

X3/11-12

When the HYDROVAR is used as a Basic drive in a multi-pump system, the X2 terminals on the power unit are
used for the serial RS-485 connection to the other HYDROVAR units in the system. (Note: Internal interface is
not available on Single Inverters!)

x2 rs485-interface – power unit

x2/ sio - Internal SIO-interface: SIO-

Internal interface

sio+ Internal SIO-interface: SIO+

for multi-pump-systems

Gnd GND, electronic ground

……. Terminals not available for HYdroVar single drives

The internal rs-485 interface on the power unit is used for the communication between up to 8 HYDROVARs
in a multi-pump system (minimum 1 Master drive). Use the same terminals to continue on to the next
HYDROVAR if required. Terminals X4/4-6 can also be used for RS-485 communication on all Master drives.

X2

GND

SIO +

rs485 – internal interface

SIO -

X1

sl

sl

ptc

ptc

SW 1

Auto

Manual

s

s

}

electrical installation and WirinG