Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 71

Advertising
background image

71

error

probable cause

Measure

• Check Parameter RAMP 1/2 [0215 /

0220] (too short) and BOOST [0265]

(too low)

oVerload

Power limit of the HYDROVAR

• Check motor connection, cable and

error 12

is exceeded

power supply

• Pump blocked

• Motor turns in the wrong direction

• MAX. FREQUENCY [0245] too high

• Parameter RAMP 2 [0220] too fast

oVerVoltaGe

DC voltage too high

• Power supply too high

error 13

• Voltage peaks too high (Solution: Line

filters)

inVert. oVerHeat

Excessive temperature inside

• Improper cooling

error 14

the HYDROVAR

• Contamination of the motor vents

• Ambient temperature too high

An external protective device

• Close X1/PTC if there is no external

connected to terminal X1/PTC

protective device connected.

tHerMo Mot/ext

has released (e.g. PTC which is

• Close external on/off switch if

error 15

connected has reached its

connected to these terminals.

release temperature).

• For detailed information, see

chapter 8.4.3.

• Check power supply under full load.

pHaseloss

One phase of the power supply

– Check if phase failure at the input.

error 16

has been lost.

• Check circuit breakers

• Visual inspection of points at the

input terminals.

• Supply voltage too low

underVoltaGe

DC voltage

• Phase failure at the input

• Asymmetry of the phase imbalance

• Check if the addressing of Basic

Inverter [DIP SW.] has been done

The communication between

correctly.

coMM lost

the Power Unit and the control

• Check if each unit has its own pump

card is lost.

address.

• Check if the connection from

control card to the power unit is

made properly (ribbon cable).

• Cut off power supply for > 60 seconds.

reset:

• Manual reset by closing external ON/OFF (Terminals X3/7-8)

• Manual reset by pressing and simultaneously for about 5 seconds

• Auto-reset possible if ERROR-RESET [0615] is set to ON

Failure MessaGes