Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 34

Advertising
background image

34

x5 status-relays

x5/ 1

CC

2

Status Relay 1

NC

[Max. 250VAC]

[250mA]

3

NO

[Max. 220VDC]

[250mA]

4

CC

[Max. 30VDC]

[2A]

5

Status Relay 2

NC

6

NO

status relay 1

status relay 2

notice:

Do not transmit any voltage or
electronic noise on these contacts.

Status Relay 1 is programmed for "Pump Run" when closed between terminals 1 and 3.
Status Relay 2 is programmed for "Fault" when closed between 4 and 5.

Factory setting: The output relays are used to signal pump-running or fault-signal.
See connection example below (To program see parameters
CONF REL 1 [0715] and CONF REL 2 [0720]).

connection examples:

pump run signal

Fault signal

X5/ 1 and 3 closed:

X5/ 4 and 5 closed:

- motor run indication

- signals a fault/error

X5

X5

6 no

5 nc

4 cc

3 no

2 nc

1 cc

X5

X5

6
5
4

3
2
1

Ext. 250VAC / 220VDC

Ext. 250VAC / 220VDC

electrical installation and WirinG