Xylem IM223 R04 Hydrovar Pump Control User Manual
Page 34
![background image](/manuals/310446/34/background.png)
34
x5 status-relays
x5/ 1
CC
2
Status Relay 1
NC
[Max. 250VAC]
[250mA]
3
NO
[Max. 220VDC]
[250mA]
4
CC
[Max. 30VDC]
[2A]
5
Status Relay 2
NC
6
NO
status relay 1
status relay 2
notice:
Do not transmit any voltage or
electronic noise on these contacts.
Status Relay 1 is programmed for "Pump Run" when closed between terminals 1 and 3.
Status Relay 2 is programmed for "Fault" when closed between 4 and 5.
Factory setting: The output relays are used to signal pump-running or fault-signal.
See connection example below (To program see parameters
CONF REL 1 [0715] and CONF REL 2 [0720]).
connection examples:
pump run signal
Fault signal
X5/ 1 and 3 closed:
X5/ 4 and 5 closed:
- motor run indication
- signals a fault/error
X5
X5
6 no
5 nc
4 cc
3 no
2 nc
1 cc
X5
X5
6
5
4
3
2
1
Ext. 250VAC / 220VDC
Ext. 250VAC / 220VDC
electrical installation and WirinG