Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 59

Advertising
background image

59

G

S

G

G

G

S

S

S

0555

0555 SWITCH INTV

Switch interval for lead / lag alternation

24 hours

(for cascade serial / synchron only!)

Possible settings:

0 – 250 hours

This parameter allows an automatic change over of the master pump and the assist pumps, to provide
even wear and achieve even operating hours of the pumps.

The switch interval is used for HYDROVAR Master Inverters only (connected via the RS-485 interface) by us-
ing operation mode Cascade Serial or Cascade Synchron.

synchronous control
By using the synchronous control mode all pumps in the system maintain the set pressure by running at the
same frequency.
The 2nd pump starts, when the 1st pump reaches the ENABLE FRQ. [0515] and the system pressure drops
below ACTU. VAL. DEC. [0510] -> both pumps will run synchronously.
The assist pump will stop, when the frequency drops below the set SYNCHR. LIMIT [0560]. This function
creates a hysteresis effect which prevents the assist pump against a frequent on/off operation.

to determine the correct setting:
• Start the first pump in JOG Mode [62]; Increase the frequency till you reach the required value. Check the

frequency ( = f0 ) at zero consumption

• Set the synchronous limit (f0 + 2..3 Hz)
• Set the synchronous window between 1 or 2 Hz (depending on the pump curve and set point).

0560

0560 SYNCHR. LIM.

Frequency limit for synchronous control

0.0 Hz

Possible settings:

0.0 Hz - Max. frequency

This parameter is used for switching off the first assist pump in synchronous mode. If the frequency of both
pumps drops below this selected value, the first assist pump stops.

0565

0565 SYNCHR. WND.

Frequency window for synchronous control

2.0 Hz

Possible settings:

0.0 – 10 Hz

Frequency limit for switching off the next assist pump.

e.g. switching off the 3rd puMp:
All 3 pumps are running at a frequency < SYNCHR. LIM. [0560] + SYNCHR. WIN. [0565]

or: switching off the 4tH puMp:
All 4 pumps are running at a frequency < SYNCHR. LIM. [0560] + 2x SYNCHR. WIN. [0565]

0570

0570 MSTPRIORITY

Master priority (for cascade serial / synchron only!)

ON

Possible settings:

ON - OFF

This parameter determines the alternation order when Master and Basic Inverters are used within one sys-
tem. In such a case you have to select if either the master or the Basic Inverters should be switched on first.

proGraMMinG