Programming – Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 48

Advertising
background image

48

If several HYDROVAR Master Inverters and even Basic Inverters are connected via the RS-485 interface, the
parameters in SUMBENU [200] can be entered on one unit and will be carried over to the other units in the
group. If programming only one unit press the button for 3 seconds and then choose the unit (1-8) for
which the parameters are being entered.

Select “ALL” to program all the units simultaneously.

Caution, if you select "ALL" the new settings will be copied to all units!

ramp settings:
• The ramps influence the rate of change in speed.
• The fast ramps 1 and 2 control the rate of acceleration and deceleration of the drive when the system

pressure is outside the hysteresis window, set at Parameter (0310). Default = 4 seconds. The ramps
should be lengthened, (increased) up to 15 seconds for higher horsepower drives to avoid overload er-
ror.

• The slow ramps 3 and 4 determine the acceleration/deceleration rates of the drive when the pressure is

within the hysteresis window. (Default = 70 sec.)

• The Ramps FminA and FminD are used for start-up and shut off. These parameters allow faster accel-

eration and deceleration and should be used for applications where pumps shouldn’t operate below a
determined frequency for a certain time. (to prevent damages or decrease wear) To adjust the Ramps,
press ▲ or ▼.

RA: Ramp F

min

acceleration

Actual Value

RD: Ramp F

min

deceleration

Output Frequency

R1: Ramp 1 – speed ramp fast increase
R2: Ramp 2 – speed ramp fast decrease
R3: Ramp 3 – speed ramp slow increase
R4: Ramp 4 – speed ramp slow decrease

set rated REQUIRED VALUE [02]

MIN FREQ [0250]

FMIN TIME [0260]

Time

RA

R3

R1

R3

R3

R3

R4

R4

R4

R4

R2

RD

Set HYSTERESIS [0315] in %

Set HYSTERESIS [0315] in %

WINDOW [0310]

setting in %

of the required

proGraMMinG