control on constant Flow

problem: control Fluctuations
cause:

check:

• Increase WINDOW [0310] and set

Control characteristics are set too low

HYSTERESIS [0315] to 99% to control with

RAMP 3 and 4.

circulating pump

problem: oscillation of the motor speed
cause:

check:

• Increase RAMP 3 [0225] and 4 [0230]:

Control settings too fast

100...200sec.

• WINDOW [0310] (20%) and HYSTERESIS [0315]

(99%).

problem: actual Value can't be maintained
cause:

check:

HYSTERESIS is set too big

HYSTERESIS [0315]: 90-99%

General

Problem: Pressure fluctuations, analogue signal not constant
Solution:

• Check cables and connection of the screen

• Check earth connection of the transmitter cable

• Use screened cables