Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 43

Advertising
background image

43

G

G

G

G

G

G

40

40 suBMenu

diaGnostics

41

41 PROD. DATE

production date of the HYDROVAR (Master/Single only)

XX.XX.XXXX

In the following parameters the current temperature, voltage and frequency of the chosen HYDROVAR can
be monitored during operation of the unit. These parameters are read only!

42

42 SEL. INVERTER

Select the desired unit

* 1 *

Possible settings:

1-8

43

43 TEMP. INVERTER

Temperature of the selected unit

XX % XX°C

The current value determines the temperature inside the selected HYDROVAR and is shown in °C and also
in percent of the maximum allowed temperature.

44

44 CURR. INVERTER

Current of the selected unit

XXX %

This value determines the output current of the HYDROVAR in percent to the maximum rated current
output.

45

45 VOLT. INVERTER

Input Voltage of the selected unit

XXX V

This value displays the input voltage supplied to the HYDROVAR.

46

46 OUTPUT FREQ.

Output frequency of the selected unit

XX.X Hz

This value displays the output frequency generated by the HYDROVAR.

47

47 VER. INVERTER

Software version of the selected drive

01

This parameter displays the software version of the BASIC drive (located on the main board).

possible indications:

00

All power sizes (2-15 HP) prior production 05/2008

01

Sizes HV 2 - 5 HP - related to control board software V01.3

02

Sizes HV7.5 - 15 - related to control board software V01.3

proGraMMinG