Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 64

Advertising
background image

64

S

S

S

S

S

S

S

S

0900 0900 suBMenu oFFset

The Offset function allows for a change in setpoint based on a separate process parameter, (ex., flow rate).
Use of this function is not recommended. Contact factory for further information.

0905

0905 OFFS. INPUT

Selection of the Offset Input

OFF

Possible settings:

OFF

analog U1 0-10V

analog U2 0-10V

analog I1 0-20mA / 4-20mA

analog I2 0-20mA / 4-20mA

0907

0907 OFFSET RANGE

Representation of the sensor range

100

Possible settings:

0 – 10000

The Offset Range can be set to a number between 0 and 10000. Its value depends on the maximum range
of the connected offset sensor.

E.g.: 300 PSI sensor can be set as range: 300; 3000; 30000

The higher the offset range the higher the resolution on the signal input.

0910

0910 LEVEL 1

Offset active between 0 and LEVEL 1

0

Possible settings:

0 – OFFSET RANGE

0912

0912 OFFSET X1

Offset signal value

0

Possible settings:

0 – LEVEL 1

Designation of the x – coordinate as absolute value.

0913

0913 OFFSET Y1

Desired value

0.00 PSI

Possible settings:

0 – standardization of the sensor

Desired value; designation of the y – coordinate as absolute value.

0915

0915 LEVEL 2

Offset active between LEVEL 2 and OFFSET RANGE

100

Possible settings:

LEVEL 1 – OFFSET RANGE

0917

0917 OFFSET X2

Offset signal value

100

Possible settings:

LEVEL 2 – OFFSET RANGE

Designation of the x – coordinate as absolute value.

proGraMMinG

Advertising