0285

0285 SKIPFRQ CTR

Skip frequency start point

0.0 Hz

Possible settings:

f

min

- f

max

0286

0286 SKIPFRQ RNG

Skip frequency range

0.0 Hz

Possible settings:

0.0 – 5.0 Hz

0290

0290 CURR. LIMIT

Current limit functionality

OFF

Possible settings:

OFF - ON

0291

0291 CURR. LIMIT

Current limit

100 %

Possible settings:

10.0 - 100 %

Previous parameters [0285] - [0291] are limited for power ratings starting from 7.5kW with production date
05/08 and control board software V01.3 → otherwise they are not visible and therefore not active.

0300

0300 suBMenu

reGulation

0305

0305 JOG 0.0Hz

Both the current output frequency and actual value are shown.

X.XX PSI

• By pressing ▲ or ▼ in this menu, the internal controller of the HYDROVAR is deactivated and it changes

to manual mode.

• Using the ▲ and ▼ buttons any constant speed can be set without further control to achieve the set

point!

• If this value becomes 0.00 Hz the HYDROVAR stops.
• As soon as the window is left by pressing or , the HYDROVAR returns to the selected mode.

0310

0310 WINDOW

Hysteresis Window

5%

Possible settings:

0 – 100% of required value

• Determines the width of the set point hysteresis window.
• For steep pump-curves and closed loop systems ~20-30%.

0315

0315 HYSTERESIS

Hysteresis for ramp switching

80%

Possible settings:

0 – 100%

• Determines the percentage of the hysteresis window, at which the ramps change from slow to fast.
• For an accurate control (without automatic shut-off) ~99%, e.g. constant flow control.