Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 49

Advertising
background image

49

G

G

G

0215

0215 RAMP 1

Ramp 1: Fast acceleration time

4 sec

Possible settings:

1 – 250 (1000) sec

• Rapid acceleration may cause an error (OVERLOAD) during drive startup.
• Slow acceleration may cause a drop in outgoing pressure during startup.

0220

0220 RAMP 2

Ramp 2: Fast acceleration time

4 sec

Possible settings:

1 – 250 (1000) sec

• Rapid deceleration may cause error (OVERVOLTAGE).
• Slow deceleration may generate over pressure.

0225

0225 RAMP 3

Ramp 3: Slow acceleration time

70 sec

Possible settings:

1 – 1000 sec

• Rapid acceleration may lead to oscillation and/or an error (OVERLOAD).
• Slow acceleration may cause a drop in outgoing pressure during varying demand.

0230

0230 RAMP 4

Ramp 4: Slow acceleration time

70 sec

Possible settings:

1 – 1000 sec

• Rapid deceleration may lead to pump oscillation.
• Slow deceleration may cause pressure fluctuations during varying demand.

0235

0235 RAMP F

MIN

A

Ramp F

min

acceleration

2.0 sec

Possible settings:

1.0 – 25.0 sec

Acceleration rate during startup until MIN. FREQUENCY [0250] is reached. Beyond the minimum frequency,
RAMP1 [0215] (fast acceleration ramp) applies.
• Rapid acceleration may cause error (OVERLOAD) during drive startup.

0240

0240 RAMP F

MIN

D

Ramp F

min

deceleration

2.0 sec

Possible settings:

1.0 – 25.0 sec

Deceleration rate applied when the drive has dropped below the MIN. FREQUENCY [0250].
• Rapid deceleration may cause error (OVERVOLTAGE)

G

G

G

proGraMMinG