• Switching between two different required values

External switching between two connected required value signals (e.g.: between voltage and current signal
input) by closing digital input 1 (X3/9-10).

In ACTUATOR mode the drive can switch between two different frequencies from the digital inputs. The
input signals (current or voltage) will be proportional to the frequency.

(For programming see SUBMENU REQUIRED VALUES [0800].)

• Actual value – Frequency Indicator

e.g. to display the actual motor frequency
How to program see SUBMENU OUTPUTS [0700].

possible connections:

Analogue output 1 (0-10V):

X3/20

Analogue output 2 (4-20mA):

X3/21

x4 rs485-interface

x4/ 1 User SIO-Interface: SIO-

User interface

2

User SIO-Interface: SIO+

for external communication

3 Gnd, electronic ground

4

Internal SIO-Interface: SIO-

Internal interface between Hydrovars

5

Internal SIO-Interface: SIO+

for multi-pump systems

6 Gnd, electronic ground

X3

X3

22

21

20

19

18

17

16

15

14

10

9

8

7

2

0 - 10V

0/4 - 20mA

Digital Input 1

(to switch between

required value 1 and

required value 2)

required Value 1

- external current signal

required Value 2

- external voltage signal

X3

20 or 21

electrical installation and WirinG