Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 40

Advertising
background image

40

08

08 AUTO - START

Auto Start

ON

Possible settings:

ON – OFF

Select ON with ▲ or OFF with the ▼ button.

If AUTO-START = ON the HYDROVAR starts automatically after reconnecting power following interruption.

If AUTO-START = OFF the HYDROVAR will not start automatically after reconnecting power following

interruption.

After reconnection of the power supply the following message is shown: AUTO START = OFF

XYLEM

XX.X Hz

Press ▲ to restart the HYDROVAR.

STOP

X.XX PSI

09

09 OPERAT. TIME

Operating hours

0000 h.

Total operating hours. To reset to 0 see parameter CLR OPERAT. [1135].

20 20 suBMenu status

Status of all units within a pump group

Use this submenu to check the status (including failures and motor hours) of all connected units.

21

21 STATUS UNITs

Status of all units

00000000

This parameter gives a quick overview about the run status of the connected drives.

• In cascade serial/synchron mode the status of all (max. 8) connected units is shown

(1=running / 0=stopped)

• In cascade relay mode the status of the 5 Relay- switching contacts is shown.

E.g. Mode – Cascade serial/synchron

21 STATUS UNITs

Unit 1, 2 and 5 are running

11001000

E.g. Mode – Cascade relay

21 STATUS UNITs

Relay Contact 1 and 3 are closed

10100 - - -

G

G

G

G

S

proGraMMinG