60 60 suBMenu settinGs

note

carefully read these instructions before changing the remaining parameters. improper
settings can cause the drive to malfunction.

These parameters can be changed during operation. Therefore they should be changed only by trained
and qualified technicians. It is recommended to stop the HYDROVAR by pressing ▼ in the main menu
before changing parameters in submenues.

61

61 PASSWORD

enter password (0066 = Default) by pressing ▲ or ▼

0000

notice! If the submenu is opened with the correct password it will remain open for a period of 10 min-
utes without entering the password again to access the secondary menu.

61 PASSWORD

Confirm by pressing and the first window of the sub menu is shown

0066

62

62 JOG

0.0Hz

Both current output frequency and actual value are shown.

X.XX PSI

• By pressing ▲ or ▼ in this menu, the drive switches from control via external input (transducer) to manual

frequency control.

• Use the ▲ and ▼ buttons to change output frequency and pump speed to achieve the desired pressure

and flow.

• If this value becomes 0.00 Hz the HYDROVAR stops.
• Exit this menu by pressing or , and the HYDROVAR returns to the previously selected mode.

0100

0100 suBMenu Basic

settinGs

0105

0105 MODE

Select the operating mode

Controller

Possible settings: Controller, Cascade Relay, Cascade Serial, Cascade Synchron, Actuator

proGraMMinG