Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 46

Advertising
background image

46

In actuator mode the drive can work with pre-selected frequencies for manual control of the HYDROVAR.
Two different frequencies can be set in the submenu REQUIRED VALUES [0800]. Switch between these
frequencies using parameter SW REQ. VAL [0815].

0106

0106 PUMP ADDR.

Select desired address for the Master Inverter

* 1 *

Possible settings:

1-8

Set desired address on each Master Inverter and press button for approximately 3 seconds and the
following messages will appear:

Addressing

->

1220 PUMP ADDR.

or

1220 PUMP ADDR.

Addressing

* 1 *

- 1 -

Address Set

Address failed - retry

When using Master and Basic drives together in a multi-pump system the Basic Inverters have separate ad-
dresses. For detailed Information see chapter 8.4.3.2 Addressing.

0110

0110 SET PASSW.

Set Password by pressing ▲ or ▼

0066

Possible settings:

0000 - 9999

caution: Resetting the password is not recommended! However, the pre-set password (0066) can be
changed. After the password has been changed, the new password should be recorded where multiple
people have access to it.

0115

0115 LOCK FUNCT.

Change with ▲ or ▼

OFF

Possible settings:

ON - OFF

f[Hz]

1/3

2/3

3/3

OF

ON

0Vdc
0mA
4mA

10Vdc
20mA
20mA

= signal range *

f min

+ zeropoint

f max

fmin

fmax

[0255] f ->min
[0255] f ->0

range of control

S

proGraMMinG