68

S

1210

1210 BAUDRATE

Baudrate for user interface

9600

Possible settings:

1200, 2400, 4800, 9600, 14400, 19200, 38400

1215

1215 FORMAT

Format for user interface

RTU N81

Possible settings:

RTU N81, RTU N82, RTU E81, RTU O81,

ASCII N72, ASCII E71, ASCII O71

internal interface
If several Master Inverters are connected via the internal RS-485 interface (maximum 8 / using cascade se-
rial mode) each HYDROVAR needs its own allocated pump-address number (1-8). each address may only

be used once!

1220

1220 PUMP ADDR.

Select desired address for the Master Inverter

1

Possible settings:

1 - 8

Set desired address for the current Master Inverter and press button for approximately 3 seconds and
the following messages will appear:

Addressing

->

1220 PUMP ADDR.

or

1220 PUMP ADDR.

Addressing

* 1 *

- 1 -

Address Set

Address failed - retry

When using Master and Basic Inverters together in a multi-pump system the Basic Inverters require a
separate address.

For detailed Information see chapter 8.4.3.2 Addressing.

proGraMMinG