Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 50

Advertising
background image

50

G

G

G

G

G

0245

0245 MAX. FRQ.

Maximum frequency

60 Hz

Possible settings:

30.0 – 70.0 Hz

This parameter determines the maximum frequency output to the motor. This should be set to the motor
nominal frequency. Default is 60 Hz.

settings higher than motor nominal frequency may overload the motor! settings of 10%

above nominal frequency increase power consumption by 33%

0250

0250 MIN. FRQ.

Minimum frequency

20.0 Hz

Possible settings:

0.0 – f

max

At operation below MIN. FREQUENCY (0250) the HYDROVAR operates with the fast ramps F

min

A and D,

(0235/0240).

the pump type and application should be considered when setting Min. FreQ. For

submersible applications the min. frequency must be set to ~30Hz.

0255

0255 CONF. F

MIN

Operation at minimum frequency

f -> 0

Possible settings:

f->0 or f->f

min

f->0: After reaching the required pressure with no demand the frequency drops to the selected MINIMUM
FREQUENCY [0250] and the HYDROVAR will continue to run for the selected F

MIN

TIME [0260]. After this

time the HYDROVAR will stop automatically.
f->f

min

: The pump will never stop automatically. The frequency will only drop down to the selected MINI-

MUM FREQUENCY [0250]. To stop the pump the external ON/OFF (E-stop) must be opened or the ▼
(Stop) button must be pressed.
applications: circulation systems

caution: The setting f->f

min

can overheat the pump if there is no flow through the pump.

Use when there is a bypass line for circulation pumps!

0260

0260 F

MIN

TIME

Delay time before shut off below MIN. FREQ.

0 s

Possible settings:

0 – 100 sec

After running below MIN. FREQ.for this selected time, the pump will stop if parameter CONFIG. FMIN
[0255] is set to f -> 0.

0265

0265 BOOST

Motor starting voltage in % of connected supply voltage

5 %

Possible settings:

0 – 25% of the input voltage

This parameter determines the characteristics of the voltage/frequency curve. In particular, it refers to the
voltage increase during startup as a percentage of the nominal voltage. This setting should be kept as low
as possible to protect the motor from thermal overload at lower frequencies. If the boost is set too low, a
failure (OVERLOAD) may occur because the starting current is too high.

proGraMMinG

Advertising