Xylem IM223 R04 Hydrovar Pump Control User Manual

Page 36

Advertising
background image

36

9.3 Basic drive display

status led - green

Constant

Motor stopped (Standby)

Blinking

Motor run

error led - red

The type of error is indicated by the number of blinks of the red ERROR LED.

1 blink

Undervoltage

2 blinks

Overcurrent / Overload

3 blinks

Drive thermal overload

4 blinks

Overvoltage

5 blinks

Code Error

6 blinks

Motor thermal overload (external contact is open)

For detailed information see chapter 11 Failure messages.

9.4 software parameters

in the following chapters all parameters of the main menu and submenus are listed. the upper window

shows the factory setting and the line below the possible range of settings. The general parameter descrip-
tion is written for the HYDROVAR Master Inverter (Full featured HYDROVAR including the high level control card
which also supports the optional modules like the optional Relay Card and all specific software features).

When using a HYdroVar single drive there are fewer software features available than with the HYDROVAR
Master drive. All parameters which are not active for the HYDROVAR Single drive are marked with the following
symbol:

… parameter not available for HYdroVar single drive

proGraMMinG

S